Sunny Central 400MV / 500MV / 630MV

Search green products
Search green companies
Sunny Central 400MV / 500MV / 630MV
Central Inverters
SUNNY CENTRAL- High Tech for solar power stations
We have developed the Sunny Centrals specially for use in large PV power stations and open-field plants. Hence they possess completely special properties. String monitoring, capacity for teamwork and the ability to feed into the medium-voltage power grid make them first choice for PV systems with homogenous structure.
Sunny Central 400MV / 500MV / 630MV
for direct medium-voltage feed-in
The compact station for safe grid management
Equipped with an SMA central inverter of the new HE product line and a medium-voltage transformer, the Sunny Central MV feeds directly into the medium-voltage grid. By removing the need for low-voltage transformers and simultaneously employing the amorphous transformer, efficiency is increased and, at the same time, inverter costs are lowered. The Sunny Central MV is delivered as a turnkey concrete substation for outside installation.
Efficient
- Greater efficiency without lowvoltage transformers due to direct connection to the medium-voltage grid
Turnkey delivery
- Complete with medium-voltage transformer and concrete substation for outdoor installation
Optional
- Medium-voltage switchgear systems for a flexible structure in designing large PV farms
- AC transfer station with measurement
- Medium-voltage transformers for other grid voltages (deviating from 20 kV)
- Amorphous transformer for minimal open circuit losses
|
Sunny Central 400MV |
Sunny Central 500MV |
Sunny Central 630MV |
|
| Input (DC) | |||
| Max. DC power (@ cos φ=1) | 455 kW | 567 kW | 723 kW |
| Max. input voltage | 1000 V | 1000 V | 1000 V |
| MPP voltage range (@ 25 °C / @ 45 °C at 50 Hz) 1) | 450 V - 820 V / 450 V - 820 V | 450 V – 820 V 1) | 500 V – 820 V / 500 V – 820 V |
| MPP voltage range (@ 25 °C at 60 Hz) 1) | 450 V – 820 V | 450 V – 820 V 1) | 510 V – 820 V |
| Rated input voltage | 500 V | 500 V | 550 V |
| Max. input current | 993 A | 1242 A | 1422 A |
| Minimum input voltage | 450 V | 450 V | 500 V |
| Number of independent MPP inputs | 1 | 1 | 1 |
| Number of DC inputs | (8+8) + 2 DCHV | (8+8) + 2 DCHV | (8+8) + 2 DCHV |
| Output (AC) | |||
| Rated power (@ 25 °C) / nominal AC power (@ 45 °C) | 440 kVA / 400 kVA | 550 kVA / 500 kVA | 700 kVA / 630 kVA |
| Nominal AC voltage / range | 20000 V / 18000 V – 22000 V | 20000 V / 18000 V – 22000 V | 20000 V / 18000 V – 22000 V |
| AC power frequency / range | 50 Hz, 60 Hz / 47 Hz ... 63 Hz | 50 Hz, 60 Hz / 47 Hz ... 63 Hz | 50 Hz, 60 Hz / 47 Hz ... 63 Hz |
| Rated power frequency / rated power frequency | 50 Hz / 20000 V | 50 Hz / 20000 V | 50 Hz / 20000 V |
| Max. output current | 12.7 A | 15.9 A | 20.2 A |
| Max. THD | < 3 % | < 3 % | < 3 % |
| Power factor at rated power / adjustable shift factor | 1 / 0.9 overexcited ... 0.9 underexcited | 1 / 0.9 overexcited ... 0.9 underexcited | 1 / 0.9 overexcited ... 0.9 underexcited |
| Feed-in phases / connection phases | 3 / 3 | 3 / 3 | 3 / 3 |
| Efficiency 2) | |||
| Max. efficiency / European efficiency | 97.5 % / 97.1 % | 97.7 % / 97.3 % | 97.8 % / 97.4 % |
| Protection | |||
| Input side disconnection device | Motor-driven DC switch-disconnector | Motor-driven DC switch-disconnector | Motor-driven switch-disconnector on DC side |
| Output side disconnection device | AC fuse-switch-disconnector | AC fuse-switch-disconnector | AC fuse-switch-disconnector |
| DC overvoltage protection / AC overvoltage protection | Surge arrester type II / surge arrester type I | Surge arrester type II / surge arrester type I | Surge arrester type II / surge arrester type I |
| Grid monitoring | yes | yes | yes |
| Ground fault monitoring / Remote ground fault monitoring | yes / opt. | yes / opt. | yes / opt. |
| Insulation monitoring | yes | yes | yes |
| Galvanic isolation | yes | yes | yes |
| Surge arrester for auxiliary supply | yes | yes | yes |
| Protection class (as per IEC 62103) | I | I | I |
| General Data | |||
| Dimensions (W / H / D) |
5300 / 3600 / 2500 mm (208.7 / 141.7 / 98.4 inch) |
5300 / 3600 / 2500 mm (208.7 / 141.7 / 98.4 inch) |
5300 / 3600 / 2500 mm (208.7 / 141.7 / 98.4 inch) |
| Weight | 30000 kg / 66139 lb | 30000 kg / 66139 lb | 30000 kg / 66139 lb |
| Operating temperature range | -20 °C ... +45 °C / -4 °F ... +113 °F | 20 °C ... +45 °C / -4 °F ... +113 °F | -20 °C ... +45 °C / -4 °F ... +113 °F |
| Max. self-consumption (in operation) / self-consumption (at night) | 1500 W 3) / < 100 W + 720 W 5) | 1500 W 3) / < 100 W + 720 W 5) | 1500 W 3) / < 100 W + 860 W 5) |
| External auxiliary supply voltage / External back-up fuse for auxiliary supply | 3 x 230 V, 50 / 60 Hz / B 20 A, 3 Pole | 3 x 230 V, 50 / 60 Hz / B 20 A, 3 Pole | 3 x 230 V, 50 / 60 Hz / B 20 A, 3-pole |
| Cooling concept | Forced cooling | Forced cooling | Forced cooling |
| Degree of protection: electronics / connection area (as per IEC 60529) | IP20 / IP54 | IP20 / IP54 | IP20 / IP54 |
| Application | Unprotected outdoors | Unprotected outdoors | Unprotected outdoors |
| Maximum permissible value for relative humidity (non-condensing) | 15 % ... 95 % | 15 % ... 95 % | 15 % ... 95 % |
| Maximum operating altitude above MSL | 1000 m | 1000 m | 1000 m |
| Fresh air consumption | 6200 m³/h | 6200 m³/h | 6200 m³/h |
| Features | |||
| DC terminal | Ring terminal lug / cage terminal | Ring terminal lug / cage terminal | Ring terminal lug / cage terminal |
| AC terminal | Ring terminal lug | Ring terminal lug | Ring terminal lug |
| Display | LC text display | LC text display | LC text display |
| Communication interfaces / Sunny String-Monitor | Ethernet, modbus / RS485 | Ethernet, modbus / RS485 | Ethernet, modbus / RS485 |
| Analog inputs / overvoltage protection for analog inputs | 2 x Ain 4) / opt. | 2 x Ain 4) / opt. | 2 x Ain 4) / opt. |
| Internal power supply transformer | opt. | opt. | opt. |
| Medium-voltage transformer with amorphous core | opt. | opt. | opt. |
| Medium-voltage switchgear | opt. | opt. | opt. |
| Color of enclosure / door / base / roof | RAL 7035 / 7024 / 7024 / 7024 | RAL 7035 / 7024 / 7024 / 7024 | RAL 7035 / 7024 / 7024 / 7024 |
| Certificates and approvals (more upon request) | EN 61000-6-2, EN 61000-6-4, EMC conformity, CE conformity, BDEW-MSRL / FGW / TR8 6), Arrêté du 4/23/08, R.D. 1663 / 2000, R.D. 661 / 2007 | EN 61000-6-2, EN 61000-6-4, EMC conformity, CE conformity, BDEW-MSRL / FGW / TR8 6), Arrêté du 4/23/08, R.D. 1663 / 2000, R.D. 661 / 2007 | EN 61000-6-2, EN 61000-6-4, EMC conformity, CE conformity, BDEW-MSRL / FGW / TR8 6), Arrêté du 4/23/08, R.D. 1663 / 2000, R.D. 661 / 2007 |
| Type designation | SC 400MV-11 | SC 500MV-11 | SC 630MV-11 |
| HE: High Efficiency, inverter without galvanic isolation for connection to a medium-voltage transformer (taking into account the SMA specification for the transformer) | |||
|
1) At 1.05 VAC, nom and cos φ = 1 2) Efficiency measured without an internal power supply at VDC = 500 V 3) Maximum power in a phase for each inverter < 1400 W (asymmetrical consumption) 4) Each with 1x irradiation sensor and 1x pyranometer 5) Disconnected according to the transformer’s open circuit losses and inverter consumption 6) Applies to BDEW-MSRL/FGW/TR8: with limited dynamic grid support |
|||
| Please note: In certain countries the substations may differ from the concept shown in the images. |
Additional Information
- manufacturer: SMA Solar Technology / Germany /